Description
RTS151 System Sensor, Remote Test Station, With Switch, Alarm, And Power LED.
The RTS151 System Sensor is an automatic fire detector accessory designed to test a remotely located detector. Consult detector installation instructions for additional information.
The National Fire Protection Association has published codes, standards, and recommended practices for the installation and use of the above product.
It is recommended that the installer be familiar with these requirements, with local codes, and any special requirements of the local authority having jurisdiction.
Specifications
- Dimensions: 4.8˝ H × 2.90˝ W × 1.4˝ D.
- Weight: .16 lbs.
Power Requirements
- Alarm LED: 2.8 – 32 VDC, 10 mA max.
- Coil Current: 95 mA max.
- Test Switch: 10 VA @ 32 VDC.
- Reset Switch: 10 VA @ 32 VDC.
- Alarm Response Time: 40 sec. max.
- Temperature: –10°C to 60°C (14°F to 140°F).
- Humidity: 95% RH Non-condensing Max.
- Listing: UL, FM, CE.
RTS151 System Sensor Contents
- 1 RTS151 remote test station.
- 1 screw pack (2 mounting screws).
- 1 M02-04 test magnet.
Wiring of RTS151 System Sensor
Consult the appropriate detector installation instructions for the applicable wiring diagram. The RTS151 System Sensor mounts to a single gang box (2 1/2” minimum depth), or directly to the wall or ceiling. In Canadian applications, the RTS151 is intended to be located in the same room as the smoke detector and within 60 feet of the unit.
Operation
Test Function
Place and hold the painted side of the magnet to the test location RTS151.
Alarm Indication
With the magnet in place some time will elapse (40 sec. maximum) depending on the detector type, before the alarm indicating LED will light.
Reset Function
Gently insert a 1/8˝ maximum diameter tool into the hole until it stops and LED turns off. The RTS151 System Sensor is capable of resetting only certain System Sensor models of detectors. Refer to detector installation instructions for additional information.
Datasheet RTS151.
See all our parts for System Sensor