4090-9007 SIMPLEX, 4008 ADDRESSABLE SIGNAL ZAM.
4090-9007 Simplex, Signal IAMs provide additional selective signaling for Simplex® 4007ES, 4008, 4010ES, 4100ES, andm 4100U Series fire alarm control panels:
- Signal output notification appliance circuit (NAC) wiring is supervised and connected to the signal input under IDNet communications control.
- NAC output is rated 0.5 A for Special Application or Regulated 24 VDC Appliances, or for audio operation (12.5 W @ 25 VRMS, 35 W @ 70.7 VRMS); and can be wired Class B or Class A.
- Signal coding of horn/strobe control, strobe synchronization, or other coding is provided by the signal input; coding at the Signal IAM via IDNet addressable communications is not supported.
- 4100U compatibility requires Software Revision 11.11.01 or higher.
- Signal IAMs are not compatible with 4010 fire alarm control panels IDNet communications.
Supervision features:
- Relay contacts isolate signal inputs from outputs during supervision and do not monitor signal presence; signal inputs sources will need to be monitored separately.
- During supervision, signal outputs are isolated from signal inputs by open contacts allowing consideration for use with SCIF applications (Sensitive Compartmented Information Facilities).
Operation details:
- Signal IAM operation is powered and supervised by the IDNet addressable communications loop – separate 24 VDC is not required for the IAM – separate signal power is required for the on-board NAC.
- Signal IAM communications use a single physical address; however, each Signal IAM reduces the IDNet loop capacity by two addresses to accommodate the extra power required for output NAC supervision.
Compact construction:
- Mounts in standard 4” square electrical box.
- Visible LED flashes to indicate communications.
- Optional covers are available to allow LED to be viewed after installation.
- Screw terminals for wiring connections.
Additional NAC Operation. For applications requiring additional individual NAC supervision and control, the 4090-9007 Signal IAM provides a 0.5 A remote NAC under host panel addressable point control. IDNet communications monitor the Signal IAM status and then connects the output NAC to the separate signal input for local alarm notification. NOTE: The Signal IAM provides additional NACs to the host control panel, it does not provide additional power. Audio Control. The Signal IAM also allows the control panel to use IDNet communications to control audio circuits from a compatible Simplex audio control panel. Only one signal source is used per Signal IAM, separate Signal IAMs would be required for control of DC powered appliances such as strobes. NOTE: Firefighter phone circuits are not supported.
UL Listed to Standard 864
Datasheet 4090-9007.