Description
49MTV-WRF SIMPLEX, MTV, WALL RED FIRE.
49MTV-WRF Simplex, TrueAlert ES addressable multi-tone A/Vs are individually addressed audible/visible notification appliances that receive power, supervision, and control signals from a Simplex fire alarm control panel providing IDNAC Signaling Line Circuits (SLCs).
Strobe Application Reference
Proper selection of visible notification is dependent on occupancy, location, local codes, and proper applications of: the National Fire Alarm Code (NFPA 72), ANSI A117.1; the appropriate model building code: BOCA, ICBO, or SBCCI; and the application guidelines of the Americans with Disabilities Act (ADA).
Individually addressed and controlled multi-tone and multi-candela TrueAlert ES A/V (audible/visible) notification appliances provide:
- Multi-candela xenon strobe with synchronized 1 Hz flash rate and with intensity programmable from the control panel or jumper selected as 15, 30, 75, 110, 135, or 185 cd.
- Advanced addressable notification controlled by IDNAC SLCs providing regulated 29 VDC allowing strobes to operate with lower current even under battery backup.
- Wiring supervision to each appliance allowing “T-tapped” connections for Class B circuits to simplify wiring (Class A circuits require in/out wiring).
- Self-Test Mode allows on-board sensors to detect the strobe and horn output and then report their status to the control panel.
- Per appliance tone selection of: 520 Hz Horn, Broadband Horn, Bell, Chime, High/Low, Slow Whoop, or Siren; programmable from the control panel, or selected using an on-board DIP Switch.
- 520 Hz tone is compliant with NFPA 72 Low Frequency Signal Requirements for Sleeping Areas.
- Horn, Bell, and High/Low tones can be controlled as: Temporal Code 3, Temporal Code 4, March Time (selectable as 20, 60, or 120 bpm), or Continuous.
- Slow Whoop, Siren, and Chime tone selections are controlled as synchronized continuous operation.
- Output of “high” or “low” (~6 dBA difference) selectable at the appliance or from the controller with FACP mode selected at the appliance.
- TrueAlert Device Reports at the control panel detailing appliance point ID, custom label, type, and candela setting .
- Magnet Test diagnostics to assist checkout and testing of appliances and wiring.
- Electrical test point access without removing cover
- Compatibility with ADA requirements.
- Strobe operation is listed to UL Standard 1971 and ULC Standard S526; Horn operation is listed to UL Standard 464 and ULC Standard S525.
Datasheet 49MTV-WRF.
See all our parts for Simplex.